• Murphy

Model 12 Air Temperature Sensor

The Model 12 Air Temperature Sensor is intended for use in applications that monitor slowly changing temperature. 

The unit gives approximately .5 °F (.25 °C) resolution when used with an 8-bit analog input.

Specifications Downloads
X
Specifications Drawer: 

Temperature Capability

  • Useful Operating Temperature Range: 0°F to 115°F (-18°C to 46°C)
  • Component Temperature Range: -85°F to 300°F (-65°C to 150°C)
  • Accuracy: 2% of full scale with software offset correction.

Voltage

  • Power Input Voltage: 9 to 28 VDC
  • Current Draw: 1mA
  • Cable: 2 foot length, 22 AWG, stranded
  • Clamp: 1/2” ID, provided (P/N 00-03-0392)

Temperature Sensing Range

VDC Out°C°F
0.00-180
0.25-14.55.8
0.50-11.411.5
0.75-8.217.3
1.00-523.0
1.25-1.828.8
1.501.434.5
1.754.640.3
2.007.846.0
2.251151.8
2.5014.257.5
2.7517.463.3
3.0020.669.0
3.2523.874.8
3.502780.5
3.7530.286.3
4.0033.392.0
4.2536.697.8
Literature Drawer: 